Backflow Preventer Test Report Checklist

Annual backflow prevention device testing checklist covering double check valves, reduced pressure zones, and pressure vacuum breakers per NYC DEP requirements.

NYC DEP / ASSE 5000Backflow Preventer30-60 min per device29 inspection items

Device Identification

  • Checkbox
    Record device make, model, serial number, and size
  • Checkbox
    Verify device type (DCVA, RPZA, PVB, DCDA)
  • Checkbox
    Record device location and service description
  • Checkbox
    Confirm device is the correct type for the hazard level
  • Checkbox
    Check DEP registration number matches installed device

Visual Inspection

  • Checkbox
    Inspect device for physical damage or corrosion
  • Checkbox
    Check for leaks at all connections and test cocks
  • Checkbox
    Verify shutoff valves upstream and downstream are operational
  • Checkbox
    Inspect relief valve discharge (RPZA) for continuous flow indicating failure
  • Checkbox
    Check that device is accessible for testing and maintenance
  • Checkbox
    Verify test cocks are present and functional

Differential Pressure Testing

  • Checkbox
    Connect calibrated differential pressure test kit
  • Checkbox
    Test first check valve for proper closure and record differential pressure
  • Checkbox
    Test second check valve for proper closure and record differential pressure
  • Checkbox
    Test relief valve opening point (RPZA) and record differential pressure
  • Checkbox
    Verify all readings meet minimum performance standards
  • Checkbox
    Record upstream supply pressure

Pass/Fail Determination

  • Checkbox
    First check valve holds minimum 1.0 PSI differential (DCVA) or 5.0 PSI (RPZA)
  • Checkbox
    Second check valve holds minimum 1.0 PSI differential
  • Checkbox
    Relief valve opens at minimum 2.0 PSI above second check closing point (RPZA)
  • Checkbox
    Air inlet opens at 1.0 PSI above atmospheric (PVB)
  • Checkbox
    Check valve holds minimum 1.0 PSI above atmospheric (PVB)
  • Checkbox
    Mark device as PASS or FAIL based on all test results

Reporting and Compliance

  • Checkbox
    Complete NYC DEP Backflow Test Report form
  • Checkbox
    Record all test gauge readings and serial numbers
  • Checkbox
    Submit test report to DEP within 30 days of test date
  • Checkbox
    Provide copy of test report to building owner or manager
  • Checkbox
    Schedule repair and retest if device failed
  • Checkbox
    Update device testing records and next due date