Fire Door Inspection Checklist — NFPA 80

Annual fire door and fire damper inspection checklist per NFPA 80. Covers door assembly, hardware, signage, self-closing devices, gap measurements, and frame integrity.

NFPA 80Fire Door5-15 min per door28 inspection items

General Information

  • Checkbox
    Record door location (floor, room number, stairwell designation)
  • Checkbox
    Identify door type (swinging, sliding, rolling, folding)
  • Checkbox
    Verify fire rating label is present and legible
  • Checkbox
    Record fire rating (20-min, 45-min, 60-min, 90-min, 3-hour)
  • Checkbox
    Document door manufacturer and model if visible

Door Assembly Condition

  • Checkbox
    Inspect door for holes, breaks, or missing sections
  • Checkbox
    Check door frame for alignment and integrity
  • Checkbox
    Verify no visible damage to fire-rated glazing if present
  • Checkbox
    Confirm door and frame are not modified with unauthorized cutouts
  • Checkbox
    Inspect door edge for proper intumescent seal or smoke gasket

Hardware Inspection

  • Checkbox
    Test self-closing device — door must close and latch from full open position
  • Checkbox
    Verify latch bolt engages strike plate fully
  • Checkbox
    Check hinges for damage, missing screws, or excessive wear
  • Checkbox
    Inspect door coordinator (if double door) for proper sequencing
  • Checkbox
    Verify no unauthorized hold-open devices (doorstops, wedges, chains)
  • Checkbox
    Confirm door closer speed allows full closure without slamming

Gap Measurements

  • Checkbox
    Measure clearance under door — maximum 3/4 inch allowed
  • Checkbox
    Check gap between door and frame — must not exceed 1/8 inch plus 1/16 inch
  • Checkbox
    Verify meeting edges of double doors have proper clearance
  • Checkbox
    Document any gaps exceeding tolerances as deficiencies with photos

Signage and Markings

  • Checkbox
    Verify fire door assembly signage is posted if required by AHJ
  • Checkbox
    Confirm no signage obstructs door operation
  • Checkbox
    Check that keep closed signage is visible on both sides

Fire Damper Inspection (if applicable)

  • Checkbox
    Locate access panel for fire damper
  • Checkbox
    Visually inspect damper blades for damage or corrosion
  • Checkbox
    Verify fusible link is present and correct temperature rating
  • Checkbox
    Confirm damper operates freely without obstruction
  • Checkbox
    Document damper type and location