Kitchen Hood Suppression System Checklist — NFPA 96

Semi-annual kitchen hood fire suppression system inspection checklist per NFPA 96 and UL 300. Covers wet chemical systems, fusible links, nozzle alignment, manual pull stations, and duct cleaning verification.

NFPA 96 / UL 300Kitchen Suppression30-60 min30 inspection items

General Information

  • Checkbox
    Record system manufacturer, model, and serial number
  • Checkbox
    Verify system type (wet chemical, dry chemical, water mist)
  • Checkbox
    Document number of nozzles and coverage zones
  • Checkbox
    Record last inspection date and service company
  • Checkbox
    Confirm UL 300 listing is current for system type

Suppression Agent and Cylinder

  • Checkbox
    Verify suppression agent cylinder is properly mounted and secured
  • Checkbox
    Check cylinder pressure gauge is in normal range
  • Checkbox
    Confirm safety pins and tamper indicators are intact
  • Checkbox
    Verify correct agent type and quantity per system design
  • Checkbox
    Check expiration date on agent cylinder

Nozzle Inspection

  • Checkbox
    Verify all nozzles are properly aimed at cooking surfaces
  • Checkbox
    Confirm nozzle caps or blow-off covers are in place
  • Checkbox
    Check nozzles for grease buildup or obstruction
  • Checkbox
    Verify nozzle spacing matches system design specifications
  • Checkbox
    Confirm no cooking equipment has been relocated from nozzle coverage area

Detection and Actuation

  • Checkbox
    Inspect fusible links for grease buildup or damage
  • Checkbox
    Verify fusible link temperature ratings are correct for location
  • Checkbox
    Replace fusible links at each semi-annual inspection
  • Checkbox
    Test manual pull station for proper operation
  • Checkbox
    Verify manual pull station is accessible and clearly marked
  • Checkbox
    Confirm gas valve automatic shutoff operates on system activation

Piping and Distribution

  • Checkbox
    Inspect all piping for damage, corrosion, or grease buildup
  • Checkbox
    Verify piping connections are tight and leak-free
  • Checkbox
    Confirm piping is properly supported and bracketed
  • Checkbox
    Check for any unauthorized modifications to piping layout

Hood and Duct Condition

  • Checkbox
    Verify hood is clean and properly maintained
  • Checkbox
    Check grease filters are in place and clean
  • Checkbox
    Confirm duct access panels are properly sealed
  • Checkbox
    Verify duct cleaning has been performed per NFPA 96 schedule
  • Checkbox
    Record date of last professional duct cleaning